Owner manual

Publication 193-UM006A-EN-P – October 2005
Protection Functions 2-5
Underload Warning
The following parameters are available for configuring the DeviceNet
Module's underload warning performance:
Parameter 22, UL Inhibit Time, allows the installer to inhibit an
underload indication from occurring during the motor starting
sequence. It is adjustable from 0…250 seconds.
Parameter 23, UL Warn Level, allows the installer to define the current at
which the DeviceNet Module will indicate a warning. It is
user-adjustable from 30…100% of the FLA dial setting.
The DeviceNet Module will immediately indicate an Underload warning if:
No warning currently exists
Underload Warning is enabled
UL Inhibit Time has expired
The motor current is less than the UL Warn Level
When the Underload Warning conditions are satisfied, the following will
occur:
Bit 3 in Parameter 4, War ning Status, will go to “1”
Bit 1 of Parameter 10, Device Status, will go to “1”
Communication Fault
Protection
A disruption of the communication link between the E1 Plus DeviceNet
Module and a DeviceNet network can result in the loss of application control
and/or critical process diagnostic data. Rapid communication fault detection
helps minimize potential damage due to uncontrolled or unmonitored
applications.
Comm Fault Warning
The DeviceNet Module will indicate a Comm Fault warning if:
No warning currently exists
Comm Fault Warning is enabled
The DeviceNet Module experiences a loss of communication
IMPORTANT
The Underload Warning function does not include a time
delay feature. Once the UL Inhibit Time has expired, the
Underload warning indication is instantaneous.