Rockwell Automation Publication 193-UM002I-EN-P - December 2011 93
Protective Trip & Warning Functions Chapter 3
PM – Oper. Hours, Parameter 102, allows the installer to set a number of hours
of operation. It is adjustable from 0…65,565 hours.
The E3 Overload Relay will give a PM – Oper. Hours warning indication when:
PM – Oper. Hours warning is enabled, and
Elapsed Time parameter is equal to or greater than the value set in the PM
– Oper. Hours parameter.
Upon a PM – Oper. Hours warning, the:
TRIP/WARN LED will flash an amber 15-blink pattern,
bit 14 in Warning Status, Parameter 15, will set to “1”, and
bit 1 in Device Status, Parameter 21, will set to “1”.
Queue Clearing
Using the Clear Queue, Parameter 104, the E3 Overload Relay provides the
capability to simultaneously clear/reset the:
Trip Logs, Parameters 16…20,
Warning Logs, Parameters 90…94,
Starts Counter, Parameter 96, and the
Elapsed Time Parameter 95.
If using the Preventative Maintenance Flags, the user will want to reset the Starts
Count and Elapsed Time after preventative maintenance has been performed.