User Manual

90 Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 3 Protective Trip & Warning Functions
Table 23 - Protective Warning Summary
Function
Factory
Default
Warning Level Inhibit Time
Range Default Range Default
Overload Disabled 0…100%
85%
Phase Loss
Ground Fault (193/592-EC2) Disabled Internal 1…5 A
2.0 A 0…250 s 10 s
Ground Fault (193/592-EC3) External 0.02…5 A
Stall
Jam Disabled 50…600% 150%
0…250 s 10 s
Underload 10…100%
70%
Thermistor (PTC)
Current Imbalance 10…100% 20% 0…250 s 10 s
Comm Fault
Comm Idle
Voltage Input Module
Hardware Fault
Enabled
Under Voltage L-L Disabled
0...65535 400
0…250 s 10 s
Over Voltage L-L
Voltage Unbalance 0…100 85
Phase Rotation
1…2 1
Under Frequency
0…250
58
Over Frequency
62
Under Real Power
0…32767
Over Real Power
Under Consumed kVAR
Over Consumed kVAR
Under Generated kVAR
-32767…0
Over Generated kVAR
Under Power kVA
0…32767
Over Power kVA
Under Power Factor Lagging
-100…0
-95
Over Power Factor Lagging
-90
Under Power Factor Leading
0...100
95
Over Power Factor Leading
90
The inhibit time setting parameters are applicable to both the trip and warning functions.
Overload warning setting is entered as a percentage of the thermal capacity utilized.
Must use Ground Fault Sensors (Catalog Number 193-CBCT_).
50…100% for devices with FRN 1.003 and earlier.
Available on 193/592-EC5 only.