User Manual

Rockwell Automation Publication 193-UM002I-EN-P - December 2011 89
Protective Trip & Warning Functions Chapter 3
Table 22 - Protective Trip Summary
Function Factory Default
Trip Level Trip Delay Inhibit Time
Range Default Range Default Range Default
Overload
Enabled
Trip Class
5…30
Trip Class
10
Phase Loss
0.1…25.0 s 1.0 s 0…250 s 0 s
Ground Fault (193/592-EC2)
Disabled
Internal 1…5 A 2.5 A 0.0…25.0 s 0.5 s 0…250 s 10 s
Ground Fault (193/592-EC3) External 0.02…5 A
2.5 A 0.0…25.0 s 0.5 s 0…250 s 10 s
Stall 100…600%
600% 0…250 s 10 s
Jam 50…600% 250% 0.1…25.0 s 5.0 s 0…250 s 10 s
Underload 10…100% FLA
50% 0.1…25.0 s 5.0 s 0…250 s 10 s
PTC
Current Imbalance 10…100% 35% 0.1…25.0 s 5.0 s 0…250 s 10 s
Comm Fault Enabled
Comm Idle
Disabled
Remote Trip
Voltage Input Module
Hardware Fault
Undervoltage L-L 0...65535 100
0.1…25.0 s 1.0 s
0…250 s 10 s
Overvoltage L-L
0...65535 500
Voltage Unbalance
0…100 75
Phase Rotation
1…2 1
Under Frequency 0…250 57
0.1…25.0 s 1.0 s
Over Frequency
0…250 63
Under Real Power
0…32767
Over Real Power
Under Consumed kVAR
Over Consumed kVAR
Under Generated kVAR -32767…0
Over Generated kVAR -32767…0
Under Power kVA 0…32767
Over Power kVA 0…32767
Under Power Factor Lagging -100…0 -90
Over Power Factor Lagging
-100…0 -95
Under Power Factor Leading
0...100 90
Over Power Factor Leading
0...100 95
The inhibit time setting parameters are applicable to both the trip and warning functions.
FLA Setting range and default values are dependent upon the current rating of the product. See the user manual for more information.
Phase loss trip level is factory-set at a current imbalance greater than or equal to 100% and is not user-adjustable.
Must use Ground Fault Sensors (Catalog Number 193-CBCT_).
Stall protection is only applicable during the motor starting sequence. If any phase of current falls below the programmed Stall Trip Level, stall
protection is disabled.
50…100% for devices with FRN 1.003 and earlier.
Available on 193/592-EC5 only.