User Manual

74 Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 3 Protective Trip & Warning Functions
bit 1 of Device Status, Parameter 21, will set to “1”.
OF Warn Level, Parameter 240, allows the installer to define the frequency in
which the E3 Plus Overload Relay will indicate a warning and is adjustable from
0…250 Hz.
Voltage Input Module
Detection
The E3 Plus model EC5 uses a Voltage Input Module to collect the voltage
signals of a power system. In the event that communications halt between the
voltage input module and the relay module, the E3 Plus model EC5 can issue a
trip or a warning to signify this unlikely event.
Voltage Hardware Trip
The E3 Overload Relay will trip with a Voltage Input Module Not Detected
indication if:
no trip currently exists,
Voltage Hardware Fault protection is enabled, and
improper communications with the Voltage Input Module.
When the voltage hardware fault trip conditions are satisfied, the:
TRIP/WARN LED will flash a red 1 long and 1 short blink pattern,
bit 1 in V Trip Status, Parameter 160, will set to “1”,
bit 0 of Device Status, Parameter 21, will set to “1”,
Trip Relay contact will be open, and
outputs will be placed in their Protection Fault state (if so programmed).
Voltage Hardware Warning
The E3 Overload Relay will issue a warning with a Voltage Input Module Not
Detected indication if:
no warning currently exists,
Voltage Hardware Fault warning is enabled, and
improper communications with the Voltage Input Module.
When the voltage hardware fault warning conditions are satisfied, the:
TRIP/WARN LED will flash an amber 1 long and 1 short blink pattern,
bit 1 in V Warn Status, Parameter 161, will set to “1”, and
bit 1 of Device Status, Parameter 21, will set to “1”.