User Manual

64 Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 3 Protective Trip & Warning Functions
TRIP/WARN LED will flash an amber 9-blink pattern,
bit 8 in Warning Status, Parameter 15, will set to “1”, and
bit 1 in Device Status, Parameter 21, will set to “1”.
CI Warn Level, Parameter 52, allows the installer to define the percent current
imbalance at which the E3 Overload Relay will indicate a warning. It is user-
adjustable from 10…100%.
Communication Fault
Protection
A disruption of the communication link between the E3 Overload Relay and a
DeviceNet network can result in the loss of application control and/or critical
process diagnostic data. Rapid communication fault detection helps minimize
potential damage due to uncontrolled or unmonitored applications.
Comm Fault Trip
The E3 Overload Relay will trip with a Comm Fault indication if:
no trip currently exists,
Comm Fault protection is enabled, and
the E3 Overload Relay experiences a loss of communication.
If the relay trips on a Comm Fault, the:
Network Status LED will blink red or become solid red
TRIP/WARN LED will flash a red 10-blink pattern
bit 9 in Trip Status, Parameter 14, will set to “1”
bit 0 in Device Status, Parameter 21, will set to “1”
Trip Relay contacts will open, and
outputs will be placed in their Protection Fault State (if so programmed).
IMPORTANT
The Current Imbalance Warning function does not include a time delay
feature. Once the CI Inhibit Time has expired, The CI warning indication is
instantaneous.
IMPORTANT
The Protection Fault State of OUT A and OUT B is defined by:
OUTA Pr FltState, Parameter 65
OUTA Pr FltValue, Parameter 66
OUTB Pr FltState, Parameter 71
OUTB Pr FltValue, Parameter 72