User Manual

Rockwell Automation Publication 193-UM002I-EN-P - December 2011 61
Protective Trip & Warning Functions Chapter 3
Figure 33 - PTC Sensor Characteristics per IEC-34-11-2
PTC Trip
The E3 Plus Overload Relay will trip with a PTC indication if:
no trip currently exists,
PTC Protection is enabled, and
resistance across terminals 1T1 and 1T2 is either greater than the relay’s
response resistance or less than the short-circuit trip resistance.
If the E3 Plus Overload Relay trips on a PTC, the:
TRIP/WARN LED will flash a red 8-blink pattern,
bit 7 in Trip Status, Parameter 14, will set to “1”,
bit 0 of Device Status, Parameter 21, will set to “1”,
Trip Relay contact will open, and
outputs will be placed in their Protection Fault State (if so programmed).
IMPORTANT
The Protection Fault State of OUT A and OUT B is defined by:
OUTA Pr FltState, Parameter 65
OUTA Pr FltValue, Parameter 66
OUTB Pr FltState, Parameter 71
OUTB Pr FltValue, Parameter 72
4000
1330
550
250
100
20
10
-20 °C
0 °C
TNF-20K
TNF-5K
TNF
TNF+15K
TNF+5K