User Manual
32 Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 2 Installation & Wiring
Table 13 - Per UL 508 & CSA 22.2, No. 14 with NEMA Contactors
Fuse Coordination
The following tables list Type I and Type II Fuse Coordination when used in
conjunction with Bulletin 100-C and 100-D Contactors.
Cat. No.
592-EC1, -EC2,
-EC3, -EC5
Contactor
Size
Maximum
Circuit Breaker/
Limiter
Available Fault
Current [A]
Voltage
[V]
UL Fuse [A]
RJ
_T 00 100,000 600 — 20 —
_C 0 100,000 240 30 30 FDB 3025/
LFB3070R
480 30 30 FDB 3025/
LFB3070R
600 30 30 —
1 100,000 240 60 100 FDB 3050/
LFB3035R
480 30 50 FDB 3050/
LFB3035R
600 30 50 —
2 100,000 240 100 200 FDB 3100/
LFB3150R
480 60 100 —
600 60 100 —
_D 3 100,000 240 200 350 FDB 3150/
LFB3150R
480 100 200 FDB 3125/
LFB3150R
600 100 200 FDB 3100/
LFB3150R
ATTENTION: Select the motor branch circuit protection that complies
with the NEC and any other governing regional or local codes.