User Manual

30 Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 2 Installation & Wiring
The earth ground terminal of the E3 Overload Relay shall be connected to
a solid earth ground via a low-impedance connection.
Installations employing an external ground fault sensor shall ground the
cable shield at the sensor with no connection made at the E3 Plus Overload
Relay.
The PTC thermistor cable shield shall be grounded at the E3 Plus
Overload Relay with no connection made at the opposite end.
Short-Circuit Ratings
The E3 Overload Relay is suitable for use on circuits capable of delivering not
more than the RMS symmetrical amperes listed in the following tables.
Short-Circuit Ratings
Table 10 - UL
Table 11 - IEC
Cat. No. Maximum
193-EC_ _ 592-EC_ _ Available Fault Current [A] Voltage [V]
B T 5,000 600
DC
ED10,000
F
G 18,000
H 42,000
Z 5,000
Cat. No.
Prospective
Current I
r
[A]
Conditional Short-Circuit
Current I
q
[A]193-EC_ _ 592-EC_ _ Maximum Voltage [V]
B T 1,000 100,000 690
D C 3,000
E D 5,000