Table 87 - Assembly Object Instance 104 Data Format OUTPUT COMMAND
Table 88 - Assembly Object Instance 105 Data Format COMMAND
Table 89 - Instance 110 Status Parameter Data Link Output Assembly
Table 90 - Assembly Object Instance 140 Data Format DEVICELOGIX CMD
Input Assemblies
Table 91 - Assembly Object Instance 50 Data Format TRIP STATUS
Table 92 - Assembly Object Instance 51 Data Format TRIP WARN STATUS
Table 93 - Assembly Object Instance 106 Data Format BASIC STATUS
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Fault Reset OutB OutA
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Remote Trip Fault Reset OutB OutA
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Remote
Trip
Fault Reset Output B Output A
1 Reserved
2 Network
Input 7
Network
Input 6
Network
Input 5
Network
Input 4
Network
Input 3
Network
Input 2
Network
Input 1
Network
Input 0
3 Network
Input 15
Network
Input 14
Network
Input 13
NetworI
nput 12
Network
Input 11
Network
Input 10
Network
Input 9
Network
Input 8
4 Status Parameter A (low)
5 Status Parameter A (high)
6 Status Parameter B (low)
7 Status Parameter B (high)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Remote
Trip
Fault Reset Output B Output A
1Network
Input 7
Network
Input 6
Network
Input 5
Network
Input 4
Network
Input 3
Network
Input 2
Network
Input 1
Network
Input 0
2Network
Input 15
Network
Input 14
Network
Input 13
Network
Input 12
Network
Input 11
Network
Input 10
Network
Input 9
Network
Input 8
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Faulted
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Warning Faulted
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Input2 Input1 OutA_Stat Warning Faulted