User Manual

214 Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 12 Troubleshooting
of this chapter for tips associated with troubleshooting trip and warning
conditions.
Table 9: Trip/Warn Codes
Series C and later
E3 Plus Model EC5 Only
Trip / Warning Description Trip Table
(Long Red)
Trip Code
(Short Red)
Warning Table
(Long Amber)
Warning Code
(Short Amber)
Protection
Fault
Non-Volatile
Fault
Test Trip 1 No No
Overload 2 2 Yes Yes
Phase Loss 3 Yes Yes
Ground Fault 4 4 Yes Yes
Stall 5 Yes Yes
Jam 6 6 Yes Yes
Underload 7 7 Yes Yes
PTC 8 8 Yes Yes
Current Imbalance 9 9 Yes Yes
Comm Fault 10 10 Yes No
Comm Idle 11 11 Yes No
NonVol Memory Fault 12 No No
Hardware Fault 13 No No
ConfigurationFault 13 No No
PM - # Starts
14 No No
Remote Trip 15 No No
PM Oper. Hours
15 No No
Blocked Start/Start Inhibit
16 No No
Voltage Input Module Hardware Fault 1 1 1 1 No No
Under Voltage L-L 1 2 1 2 Yes Yes
Over Voltage L-L 1 3 1 3 Yes Yes
Voltage Unbalance 1 4 1 4 Yes Yes
Phase Rotation 1 5 1 5 Yes Yes
Under Frequency 1 6 1 6 Yes Yes
Over Frequency 1 7 1 7 Yes Yes
Under Real Power (kW) 2 1 2 1 Yes Yes
Over Real Power (kW) 2 2 2 2 Yes Yes
Under Reactive Power Consumed (+kVAR) 2 3 2 3 Yes Yes
Over Reactive Power Consumed (+kVAR) 2 4 2 4 Yes Yes
Under Reactive Power Generated (-kVAR) 2 5 2 5 Yes Yes
Over Reactive Power Generated (-kVAR) 2 6 2 6 Yes Yes
Under Apparent Power (kVA) 2 7 2 7 Yes Yes
Over Apparent Power (kVA) 2 8 2 8 Yes Yes
Under Power Factor Lagging (-PF) 2 9 2 9 Yes Yes
Over Power Factor Lagging (-PF) 2 10 2 10 Yes Yes
Under Power Factor Leading (+PF) 2 11 2 11 Yes Yes
Over Power Factor Leading (+PF) 2 12 2 12 Yes Yes
Power Value Overflow (kW, kVAR or KVA) 213 2 13YesYes
IMPORTANT
The Trip conditions identified as “Protection Faults” are the
basis for the OUTA Pr FltState, OUTA Pr FltValue, OUTB Pr
FltState, and OUTB Pr FltValue parameters.