Chapter 10 Logic Controller Communication Examples
Next, set up the communications path in the Communication tab to read data
from the E3 Plus Overload Relay located at Node 6 by configuring the
communication Path as “DNET, 2, 6”
DNET - the name of the 1769-SDN DeviceNet Scanner
2 – The port number of the 1769-SDN DeviceNet Scanner
6 – The node address of the E3 Plus Overload Relay
When finished, the MSG instruction will read the Trip Class from the E3 Plus
Overload Relay and place the results in Integer_Files[2] as shown below:
Currently the Trip Class of the E3 Plus Overload Relay is configured as Class 10
as shown in Integer_Files[2].