User Manual
188 Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 9 Trip History and Snapshot
V TripHist Mask
This parameter allows the user to
configure which voltage based
protection features are written to the five
record Trip History as outlined in the
table below:
1 = Recorded
0 = Not Recorded
Parameter Number 299
Access Rule Get/Set
Data Type UINT
Object Mapping 0Fhex-12B-01
Group TripWarn History
Units —
Minimum Value 0000000000000000
Maximum Value 0000000001111111
Default Value 0000000001111111
Bit Function:
1514131211109876543210
XVoltage Hdwr Flt
XUnder Volt L-L
XOver Volt L-L
XVoltage Unbal
X Phase Rotation
X Under Frequency
XOver Frequency
V WarnHist Mask
This parameter allows the user to
configure which voltage based
protection features are written to the five
record Warning History as outlined in the
table below:
1 = Recorded
0 = Not Recorded
Parameter Number 300
Access Rule Get/Set
Data Type UINT
Object Mapping 0Fhex-12C-01
Group TripWarn History
Units —
Minimum Value 0000000000000000
Maximum Value 0000000001111111
Default Value 0000000001111111
Bit Function:
1514131211109876543210
XVoltage Hdwr Flt
XUnder Volt L-L
XOver Volt L-L
XVoltage Unbal
X Phase Rotation
X Under Frequency
XOver Frequency
PW TripHist Mask
This parameter allows the user to
configure which power based protection
features are written to the five record Trip
History as outlined in the table below:
1 = Recorded
0 = Not Recorded
Parameter Number 301
Access Rule Get/Set
Data Type UINT
Object Mapping 0Fhex-12D-01
Group TripWarn History
Units —
Minimum Value 0000000000000000
Maximum Value 0001111111111111
Default Value 0001111111111111