User Manual
Rockwell Automation Publication 193-UM002I-EN-P - December 2011 187
Trip History and Snapshot Chapter 9
Bit Function:
1514131211109876543210
XTest Trip
XOverload
X Phase Loss
X Ground Fault
XStall
XJam
XUnderload
XReserved
XCurrent Imbal
X Comm Fault
X Comm Idle
XNonVol Mem
X Hardware Fault
XReserved
X Remote Trip
X Bocked Start
WarnHistory Mask
This parameter allows the user to
configure which current based
protection features are written to the five
record Warning History as outlined in the
table below:
1 = Recorded
0 = Not Recorded
Parameter Number 143
Access Rule Get/Set
Data Type UINT
Object Mapping 0Fhex-8F-01
Group TripWarn History
Units —
Minimum Value 0000000000000000
Maximum Value 0111111111111111
Default Value 0111011101101010
Bit Function:
1514131211109876543210
XReserved
XOverload
X Phase Loss
X Ground Fault
XReserved
XJam
XUnderload
XReserved
XCurrent Imbal
X Comm Fault
X Comm Idle
XReserved
XConfig Fault
XPM Starts
XPM Oper Hours
Reserved