Chapter 9 Trip History and Snapshot
Table 8: Trip & Warning History Fault Codes
Code Type Description
0 No Fault No Fault Conditions Detected
1 Test Trip Test trip caused by holding the Test/Rest button for 2 seconds
2 Overload Motor current overload condition
3 Phase Loss Phase current Loss detected in one of the motor phases
4 Ground Fault Power conductor or motor winding is shorting to ground
5 Stall Motor has not reached full speed by the end of Stall Enable Time
6 Jam Motor current has exceed the programmed jam trip level
7 Underload Motor current has fallen below normal operating levels
8 PTC PTC input indicates that the motor stator windings overheated
9 Current Imbal Phase to phase current imbalance detected
10 Comm Fault DeviceNet communication loss detected
11 Comm Idle DeviceNet idle condition detected
12 NonVol Mem Internal memory failure. Contact the factory.
13 Hardware Fault Hardware configuration fault. Check for shorts on input terminal
15 Remote Trip Remote trip command detected
16 Blocked Start Maximum starts per hour exceeded
17 Voltage Hdw Flt A problem with the external voltage hardware has been detected
18 Under Volt L-L Line to Line Under-Voltage condition detected
19 Over Volt L-L Line to Line Over-Voltage condition detected
20 Voltage Unbal Phase to phase voltage imbalance detected
21 Phase Rotation The unit detects the supply voltage phases are rotated
22 Under Frequency Line voltage frequency is below trip level
23 Over Frequency Line voltage frequency has exceeded trip level
33 Under Real Pwr Total Real Power(kW)is below trip level
34 Over Real Pwr Total Real Power(kW)has exceeded trip level
35 Under Con kVAR Under Total Reactive Power Consumed (+kVAR) condition detected
36 Over Con kVAR Over Total Reactive Power Consumed (+kVAR) condition detected
37 Under Gen kVAR Under Total Reactive Power Generated (-kVAR) condition detected
38 Over Gen kVAR Over Total Reactive Power Generated (-kVAR) condition detected
39 Under Power kVA Total Apparent Power (VA or kVA or MVA) is below trip level
40 Over Power kVA Total Apparent Power (VA or kVA or MVA) exceeded trip level
41 Under PF Lagging Under Total Power Factor Lagging (-PF) condition detected
42 Over PF Lagging Over Total Power Factor Lagging (-PF) condition detected
43 Under PF Leading Under Total Power Factor Leading (+PF) condition detected
44 Over PF Leading Over Total Power Factor Leading (+PF) condition detected
45 Power Overflow kW, kVAR or kVA has exceeded its maximum display value
TripHistory Mask
This parameter allows the user to
configure which current based
protection features are written to the five
record Trip History as outlined in the
table below:
1 = Recorded
0 = Not Recorded
Parameter Number 142
Access Rule Get/Set
Data Type UINT
Object Mapping 0Fhex-8E-01
Group TripWarn History
Units —
Minimum Value 0000000000000000
Maximum Value 1111111111111111
Default Value 1101111101111111