UPFLD Inhibit Time
This parameter defines the amount of
time for which an under power factor
leading detection is inhibited during a
motor starting sequence.
Parameter Number 281
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-119-01
Group Power Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 10
UPFLD Trip Delay
This parameter allows the installer to
program a time duration for which an
under power factor leading condition
must exist prior to the device tripping.
Parameter Number 282
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-11A-01
Group Power Setup
Units Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0
UPFLD Trip Level
This parameter sets the under power
factor leading trip level.
Parameter Number 283
Access Rule Get/Set
Data Type SINT
Object Mapping 0Fhex-11B-01
Group Power Setup
Units %
Minimum Value 0
Maximum Value 100
Default Value 90
UPFLD Warn Level
This parameter sets the under power
factor leading warning level.
Parameter Number 284
Access Rule Get/Set
Data Type SINT
Object Mapping 0Fhex-11C-01
Group Power Setup
Units %
Minimum Value 0
Maximum Value 100
Default Value 95
OPFLD Inhibit Time
This parameter defines the amount of
time for which an over power factor
leading detection is inhibited during a
motor starting sequence.
Parameter Number 285
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-11D-01
Group Power Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 10