User Manual

Rockwell Automation Publication 193-UM002I-EN-P - December 2011 179
Power Parameters Chapter 8
UPFLG Warn Level
This parameter sets the under power
factor lagging warning level.
Parameter Number 276
Access Rule Get/Set
Data Type SINT
Object Mapping 0Fhex-114-01
Group Power Setup
Units %
Minimum Value -100
Maximum Value 0
Default Value -95
OPFLG Inhibit Time
This parameter defines the amount of
time for which an over power factor
lagging detection is inhibited during a
motor starting sequence.
Parameter Number 277
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-115-01
Group Power Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 10
OPFLG Trip Delay
This parameter allows the installer to
program a time duration for which an
over power factor lagging condition
must exist prior to the device tripping.
Parameter Number 278
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-116-01
Group Power Setup
Units Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0
OPFLG Trip Level
This parameter sets the over power
factor lagging trip level.
Parameter Number 279
Access Rule Get/Set
Data Type SINT
Object Mapping 0Fhex-117-01
Group Power Setup
Units %
Minimum Value -100
Maximum Value 0
Default Value -95
OPFLG Warn Level
This parameter sets the over power
factor lagging warning level.
Parameter Number 280
Access Rule Get/Set
Data Type SINT
Object Mapping 0Fhex-118-01
Group Power Setup
Units %
Minimum Value -100
Maximum Value 0
Default Value -90