Power Parameters Chapter 8
UVA Trip Delay
This parameter allows the installer to
program a time duration for which an
under apparent power (kVA) condition
must exist prior to the device tripping.
Parameter Number 266
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-10A-01
Group Power Setup
Units Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0
UVA Trip Level
This parameter sets the under apparent
power (kVA) trip level.
Parameter Number 267
Access Rule Get/Set
Data Type INT
Object Mapping 0Fhex-10B-01
Group Power Setup
Units kVA
Minimum Value 0
Maximum Value 32767
Default Value —
UVA Warn Level
This parameter sets the under apparent
power (kVA) warning level.
Parameter Number 268
Access Rule Get/Set
Data Type INT
Object Mapping 0Fhex-10C-01
Group Power Setup
Units kVA
Minimum Value 0
Maximum Value 32767
Default Value —
OVA Inhibit Time
This parameter defines the amount of
time for which an over apparent power
(kVA) detection is inhibited during a
motor starting sequence.
Parameter Number 269
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-10D-01
Group Power Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 10
OVA Trip Delay
This parameter allows the installer to
program a time duration for which an
over apparent power (kVA) condition
must exist prior to the device tripping.
Parameter Number 270
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-10E-01
Group Power Setup
Units Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0