User Manual

Rockwell Automation Publication 193-UM002I-EN-P - December 2011 175
Power Parameters Chapter 8
OVARC Warn Level
This parameter sets the over reactive
power (kVAR) consumed warning level.
Parameter Number 256
Access Rule Get/Set
Data Type INT
Object Mapping 0Fhex-100-01
Group Power Setup
Units kVAR
Minimum Value 0
Maximum Value 32767
Default Value
UVARG Inhibit Time
This parameter defines the amount of
time for which an under reactive power
(kVAR) generated detection is inhibited
during a motor starting sequence.
Parameter Number 257
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-101-01
Group Power Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 10
UVARG Trip Delay
This parameter allows the installer to
program a time duration for which an
under reactive power (kVAR) generated
condition must exist prior to the device
tripping.
Parameter Number 258
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-102-01
Group Power Setup
Units Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0
UVARG Trip Level
This parameter sets the under reactive
power (kVAR) generated trip level.
Parameter Number 259
Access Rule Get/Set
Data Type INT
Object Mapping 0Fhex-103-01
Group Power Setup
Units kVAR
Minimum Value -32768
Maximum Value 0
Default Value
UVARG Warn Level
This parameter sets the under reactive
power (kVAR) generated warning level.
Parameter Number 260
Access Rule Get/Set
Data Type INT
Object Mapping 0Fhex-104-01
Group Power Setup
Units kVAR
Minimum Value -32768
Maximum Value 0
Default Value