Power Parameters Chapter 8
OW Trip Delay
This parameter allows the installer to
program a time duration for which an
over real power (kW) condition must
exist prior to the device tripping.
Parameter Number 246
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-F6-01
Group Power Setup
Units Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0
OW Trip Level
This parameter sets the over real power
(kW) trip level.
Parameter Number 247
Access Rule Get/Set
Data Type INT
Object Mapping 0Fhex-F7-01
Group Power Setup
Units kW
Minimum Value 0
Maximum Value 32767
Default Value —
OW Warn Level
This parameter sets the over real power
(kW) warning level.
Parameter Number 248
Access Rule Get/Set
Data Type INT
Object Mapping 0Fhex-F8-01
Group Power Setup
Units kW
Minimum Value 0
Maximum Value 32767
Default Value —
UVARC Inhibit Time
This parameter defines the amount of
time for which an under reactive power
(kVAR) consumed detection is inhibited
during a motor starting sequence.
Parameter Number 249
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-F9-01
Group Power Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 10
UVARC Trip Delay
This parameter allows the installer to
program a time duration for which an
under reactive power (kVAR) consumed
condition must exist prior to the device
tripping.
Parameter Number 250
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-FA-01
Group Power Setup
Units Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0