User Manual

172 Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 8 Power Parameters
UW Inhibit Time
This parameter defines the amount of
time for which an under real power (kW)
detection is inhibited during a motor
starting sequence.
Parameter Number 241
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-F1-01
Group Power Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 10
UW Trip Delay
This parameter allows the installer to
program a time duration for which an
under real power (kW) condition must
exist prior to the device tripping.
Parameter Number 242
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-F2-01
Group Power Setup
Units Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0
UW Trip Level
This parameter sets the under real power
(kW) trip level.
Parameter Number 243
Access Rule Get/Set
Data Type INT
Object Mapping 0Fhex-F3-01
Group Power Setup
Units kW
Minimum Value 0
Maximum Value 32767
Default Value
UV Warn Level
This parameter sets the under real power
(kW) warning level.
Parameter Number 244
Access Rule Get/Set
Data Type INT
Object Mapping 0Fhex-F4-01
Group Power Setup
Units kW
Minimum Value 0
Maximum Value 32767
Default Value
OW Inhibit Time
This parameter defines the amount of
time for which an over real power (kW)
detection is inhibited during a motor
starting sequence.
Parameter Number 245
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-F5-01
Group Power Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 10