Chapter 8 Power Parameters
L2 PF
This parameter provides the power factor
measured in L2 with measurement in
percentage.
Parameter Number 186
Access Rule Get
Data Type SINT
Object Mapping 0Fhex-BA-01
Group Power Monitor
Units %
Minimum Value -100
Maximum Value 100
Default Value —
L3 PF
This parameter provides the power factor
measured in L3 with measurement in
percentage.
Parameter Number 187
Access Rule Get
Data Type SINT
Object Mapping 0Fhex-BB-01
Group Power Monitor
Units %
Minimum Value -100
Maximum Value 100
Default Value —
Total PF
This parameter provides the total power
factor averaged from all phases with
measurement in percentage.
Parameter Number 188
Access Rule Get
Data Type SINT
Object Mapping 0Fhex-BC-01
Group Power Monitor
Units %
Minimum Value -100
Maximum Value 100
Default Value —
kWh 10E6
This parameter provides a component of
total real energy (kWh). Multiply this
value by 10
6
and add to the other kWh
parameters.
Represents XXX,000,000.000
Parameter Number 189
Access Rule Get
Data Type INT
Object Mapping 0Fhex-BD-01
Group Power Monitor
Units
Minimum Value -32768
Maximum Value 32767
Default Value —
kWh 10E3
This parameter provides a component of
total real energy (kWh). Multiply this
value by 10
3
and add to the other kWh
parameters.
Represents 000,XXX,000.000
Parameter Number 190
Access Rule Get
Data Type INT
Object Mapping 0Fhex-BE-01
Group Power Monitor
Units
Minimum Value -999
Maximum Value 999
Default Value —