User Manual

154 Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 7 Voltage Parameters
OV Warn Level
This parameter sets the over voltage
warning level.
Parameter Number 222
Access Rule Get/Set
Data Type UINT
Object Mapping 0Fhex-DE-01
Group Voltage Setup
Units Volts
Minimum Value 0
Maximum Value 65535
Default Value 490
Ph Rot Inhibit Time
This parameter defines the amount of time
for which an improper phase rotation
detection is inhibited during a motor
starting sequence.
Parameter Number 223
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-DF-01
Group Voltage Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 10
Ph Rot Trip
This parameter sets the rotation trip and
warning direction.
Parameter Number 224
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-E0-01
Group Voltage Setup
Units 1 = ABC
2 = ACB
Minimum Value 1
Maximum Value 2
Default Value 1
V UnbalInhib Time
This parameter defines the amount of time
for which voltage unbalance detection is
inhibited during a motor starting
sequence.
Parameter Number 229
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-E5-01
Group Voltage Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 10
V UnbalTripDelay
This parameter allows the installer to
program a time duration for which a
voltage unbalance condition must exist
prior to the device tripping.
Parameter Number 230
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-E6-01
Group Voltage Setup
Units Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0