152 Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 7 Voltage Parameters
Bit Function:
1514131211109876543210
XVoltage Hardware Fault
XUnder Volt L-L
XOver Volt L-L
XVoltage Unbalance
X Phase Rotation
X Under Frequency
XOver Frequency
V Warn Enable
This parameter allows the installer to
enable or disable voltage based warning
functions separately.
1 = Warning
0 = No Warning
Parameter Number 159
Access Rule Get/Set
Data Type UINT
Object Mapping 0Fhex-9F-01
Group Voltage Setup
Units —
Minimum Value 0000000000000000
Maximum Value 0000000000111111
Default Value 0000000000000001
Bit Function:
1514131211109876543210
XVoltage Hardware Fault
XUnder Volt L-L
XOver Volt L-L
XVoltage Unbalance
X Phase Rotation
X Under Frequency
XOver Frequency
UV Inhibit Time
This parameter defines the amount of time
for which an under voltage detection is
inhibited during a motor starting
sequence.
Parameter Number 215
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-D7-01
Group Voltage Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 10
UV Trip Delay
This parameter allows the installer to
program a time duration for which an
under voltage condition must exist prior to
the device tripping.
Parameter Number 216
Access Rule Get/Set
Data Type USINT
Object Mapping 0Fhex-D8-01
Group Voltage Setup
Units Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0