Rockwell Automation Publication 193-UM002I-EN-P - December 2011 149
Voltage Parameters Chapter 7
V Warn Status
This parameter provides voltage based
warning identification as outlined in the
table below:
1 = Warning
0 = No Warning
Parameter Number 161
Access Rule Get
Data Type UINT
Object Mapping 0Fhex-A1-01
Group Voltage monitor
Units
Minimum Value
Maximum Value
Default Value
Bit Function:
1514131211109876543210
XVoltage Hardware Fault
XUnder Volt L-L
XOver Volt L-L
XVoltage Unbalance
XPhase Rotation
X Under Frequency
XOver Frequency
L1-L2 Voltage
This parameter provides the L1-L2 voltage
measurement in Volts.
Parameter Number 162
Access Rule Get
Data Type UINT
Object Mapping 0Fhex-A2-01
Group Voltage Monitor
Units Volt
Minimum Value 0
Maximum Value 65545
Default Value
L2-L3 Voltage
This parameter provides the L2-L3 voltage
measurement in Volts.
Parameter Number 163
Access Rule Get
Data Type UINT
Object Mapping 0Fhex-A3-01
Group Voltage Monitor
Units Volt
Minimum Value 0
Maximum Value 65545
Default Value
L3-L1 Voltage
This parameter provides the L3-L1 voltage
measurement in Volts.
Parameter Number 164
Access Rule Get
Data Type UINT
Object Mapping 0Fhex-A4-01
Group Voltage Monitor
Units Volt
Minimum Value 0
Maximum Value 65545
Default Value