Rockwell Automation Publication 193-UM002I-EN-P - December 2011 145
Monitoring Parameters Chapter 6
Warn Log 2 (Series C and later)
This parameter records the warning
previous to Warn Log 1.
Parameter Number 92
Access Rule Get
Data Type WORD
Object Mapping 29hex-1-111
Group Monitor
Units
Minimum Value See Warning Status Table
Maximum Value See Warning Status Table
Default Value 0
Warn Log 3 (Series C and later)
This parameter records the warning
previous to Warn Log 2.
Parameter Number 93
Access Rule Get
Data Type WORD
Object Mapping 29hex-1-112
Group Monitor
Units
Minimum Value See Warning Status Table
Maximum Value See Warning Status Table
Default Value 0
Warn Log 4 (Series C and later)
This parameter records the warning
previous to Warn Log 3.
Parameter Number 94
Access Rule Get
Data Type WORD
Object Mapping 29hex-1-113
Group Monitor
Units
Minimum Value See Warning Status Table
Maximum Value See Warning Status Table
Default Value 0
Elapsed Time (Series C and later)
This parameter records the hours of motor
operation - the time period that the E3 is
sensing motor current present (motor
current must be greater than 30% of the
minimum Full Load Current (FLA) setting).
Parameter Number 95
Access Rule Get
Data Type UINT
Object Mapping 29hex-1-100
Group Monitor
Units Hours
Minimum Value 0
Maximum Value 65535
Default Value 0
Starts Counter (Series C and later)
This parameter records the number of
starts - motor current transitions from zero
to non-zero values (motor current must be
greater than 30% of the minimum Full
Load Current (FLA) setting).
Parameter Number 96
Access Rule Get
Data Type UINT
Object Mapping 29hex-1-101
Group Monitor
Units -
Minimum Value 0
Maximum Value 65535
Default Value 0