Chapter 6 Monitoring Parameters
➊ Series C and later
WARNING STATUS
This parameter provides warning
identification.
Parameter Number 15
Access Rule Get
Data Type WORD
Object Mapping 0x29-1-115
Group Monitor
Units —
Minimum Value —
Maximum Value —
Default Value None
Bit Function:
1514131211109876543210
—
XOverload
—
X Ground Fault (E3 Plus)
—
XJam
XUnderload
XPTC (E3 Plus)
XCurrent Imbalance
X Comm Fault
X Comm Idle
—
XConfig Fault
XPM - # Starts
➊
XPM – Oper. Hours➊
TRIP LOG 0
This parameter records the latest trip.
Parameter Number 16
Access Rule Get
Data Type WORD
Object Mapping 0x29-1-116
Group Monitor
Units —
Minimum Value See Trip Status table
Maximum Value See Trip Status table
Default Value None
TRIP LOG 1
This parameter records the trip previous to
Trip Log 0.
Parameter Number 17
Access Rule Get
Data Type WORD
Object Mapping 0x29-1-117
Group Monitor
Units —
Minimum Value See Trip Status table
Maximum Value See Trip Status table
Default Value None