User Manual

Rockwell Automation Publication 193-UM002I-EN-P - December 2011 137
Monitoring Parameters Chapter 6
Ground Fault Current
Reporting
Current Range
The following chart illustrates the minimum and maximum reporting ground
fault current values for a given ground fault current range.
The E3 Plus Overload Relay will report 0 A if the ground fault current is below 50% of the minimum ground fault
current setting for a given range.
The E3 Plus Overload Relay is capable of reporting values greater than the maximum values shown, but the
accuracy of the value is compromised.
The accuracy specified is only applicable to non-distorted sinusoidal currents.
20…100 mA for resistive loads only. For motor loads, consult your local Rockwell Automation sales office or
Allen-Bradley distributor.
Frequency Range
The E3 Plus Overload Relay is capable of sensing variable frequency ground fault
currents ranging from 20…250 Hz.
Exception: Any E3 Plus Overload Relay using an external ground fault sensor is
limited to 50/60 Hz detection.
Diagnostic Parameters
The E3 Overload relay provides a number of motor diagnostic parameters to
assist maintenance personnel with information to minimize unplanned down
time. The relay also provides a number of preventative maintenance diagnostics
to maximize the life of an electric motor.
Table 3: Ground Fault Current Reporting Summary
Ground Fault
Current Range
Minimum
Reporting
Current ➊➌
Maximum
Reporting
Current ➋➌
E3 Plus Cat. No. /Series
20…100 mA 10 mA 180 mA 193/592-EC3 and -EC5 — Series C
and later
100…500 mA 50 mA 900 mA 193/592-EC3 and -EC5 — Series C
and later
200 mA…1.0 A 100 mA 1.80 A 193/592-EC3 and -EC5 — Series C
and later
1.0…5.0 A 500 mA 9.00 A 193/592-EC2 and -EC5 — Series A
and later