Rockwell Automation Publication 193-UM002I-EN-P - December 2011 125
Programmable Parameters Chapter 5
DeviceNet Setup Group
Table 61 - Assembly Parameters Detail
CLEAR QUEUE (Series C and later)
This parameter allows the user to clear the
Trip Logs, Warning Logs, Starts Counter,
and the Elapsed Time. Setting the Clear
Queue parameter to "1" will clear/reset the
Trip Logs, Warning Logs, Starts Counter,
and the Elapsed Time parameters at the
same time.
Parameter Number 104
Access Rule Get/Set
Data Type BOOL
Object Mapping 29hex-1-132
Group Reset/Lock
Units —
Minimum Value 0 = Ready
Maximum Value 1 = Clear
Default Value 0
OUTPUT ASSEMBLY
This parameter is used to select the desired
output assembly. See Appendix B for a
listing of available assemblies
Parameter Number 59
Access Rule Get/Set
Data Type USINT
Object Mapping 0xB4-1-16
Group DeviceNet Setup
Units —
Minimum Value 0
Maximum Value 105
Default Value 103 (E3)
105 (E3 Plus)
INPUT ASSEMBLY
This parameter is used to select the desired
input assembly. See Appendix B for a
listing of available assemblies
Parameter Number 60
Access Rule Get/Set
Data Type USINT
Object Mapping 0xB4-1-17
Group DeviceNet Setup
Units —
Minimum Value 0
Maximum Value 107
Default Value 100
ASSY WORD0 PARAM
This parameter assigns the parameter
value to be placed in Word 0 of Input
Assembly 100.
Parameter Number 61
Access Rule Get/Set
Data Type USINT
Object Mapping 0xB4-1-7
Group DeviceNet Setup
Units —
Minimum Value 0
Maximum Value 302 ➊
Default Value 21
ASSY WORD1 PARAM
This parameter assigns the parameter
value to be placed in Word 1 of Input
Assembly 100.
Parameter Number 62
Access Rule Get/Set
Data Type USINT
Object Mapping 0xB4-1-8
Group DeviceNet Setup
Units —
Minimum Value 0
Maximum Value 302 ➊