User Manual
122 Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 5 Programmable Parameters
Table 57 - Two-Speed Motor Parameters Detail — E3 Plus
Table 58 - Preventative Maintenance Parameters Detail
2-SPD NET ENABLE
This parameter allows the use of Output
Assemblies 104 and 105 for two-speed
applications.
Parameter Number 87
Access Rule Get/Set
Data Type BOOL
Object Mapping 2C
hex
-1-154
Group Advanced Setup
Units —
Minimum Value 0 = Disabled
Maximum Value 1 = Enabled
Default Value 0
2-SPEED FLA SET
This parameter allows the user to program
the high speed FLA value of a two-speed
motor.
Parameter Number 88
Access Rule Get/Set
Data Type UINT
Object Mapping 2C
hex
-1-155
2C
hex
-1-156
2C
hex
-1-157
Group Advanced Setup
Units Amps
Minimum Value See Table 41 on page 112
Maximum Value See Table 41 on page 112
Default Value See Table 41 on page 112
PM - # Starts (Series C and later)
This parameter allows the installer to set a
number of starts after which preventative
maintenance should be performed.
Parameter Number 101
Access Rule Get/Set
Data Type UINT
Object Mapping 29hex-1-106
Group Advanced Setup
Units —
Minimum Value 0
Maximum Value 65535
Default Value 0
PM - Oper. Hours (Series C and later)
This parameter allows the installer to set
the hours of operation after which
preventative maintenance should be
performed.
Parameter Number 102
Access Rule Get/Set
Data Type UINT
Object Mapping 29hex-1-107
Group Advanced Setup
Units Hours
Minimum Value 0
Maximum Value 65535
Default Value 0