User Manual

12 Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 1 Product Overview
Catalog Number
Explanation
The solid-state overload relay purchased has its own catalog number. The catalog
number is explained below.
Single-/Three-Phase
Operation
The overload relay is factory programmed for three-phase operation. The
installer can easily be changed to single-phase operation by accessing and
changing Single/Three Phase, Parameter 27. Refer to page 34 for typical motor
connections.
Protection & Warning
Functions
The E3 Overload Relay provides the following protection and warning functions:
Refer to Chapter 3 on page 45 for further explanation of these protection and
warning functions.
193 - EC1 B B
592
Bulletin
Number
Type
EC1 E3
EC2 E3 Plus
EC3 E3 Plus
EC5 E3 Plus
Current Rating
(Amps)
P0.42.0
A15
B 3…15
C 5…25
D 9…45
E1890
F28140
G42210
H60302
J84420
K 125…630
L 172…860
Bulletin 500
Contactor Size
T Size 00
C Size 0…2
D Size 3
E Size 4
F Size 5
G Size 6
Bulletin 100 Contactor
Size
B C09…C23
D C30…C43
E C60…C85
F D95…D180
G D210…D420
H D630…D860
ZPanel Mount, CT fed
(0.4…90 A) Provides 1…5 A internal core-balanced ground fault protection
(0.4.…5000 A) Provides 20 mA…5 A external core balanced ground fault protection. External ground fault
sensor required (Cat. nos. 193-CBCT-1…4).
Function Model
Overload
Phase loss (trip only)
Stall (trip only)
Jam
Underload
Current imbalance
Number of starts (warning only)
Operating hours (warning only)
All Models
Voltage
Power
Frequency
EC5 Only
Ground fault EC2, EC3, & EC5 Only
Thermistor (PTC) input EC2 and EC3 Only