User Manual
Rockwell Automation Publication 193-UM002I-EN-P - December 2011 117
Programmable Parameters Chapter 5
Table 51 - Start Parameters Detail — Series C & Later
GF SENSING RANGE
(E3 Plus, Series C and later)
This parameter selects one of the
Ground Fault Sensing Ranges:
20…100 mA ➊
100…500 mA
200 mA…1.0 A
1.0…5.0 A
Parameter Number 106
Access Rule Get/Set
Data Type USINT
Object Mapping 2Chex-1-181
Group Advanced Setup
Units 0 = 20…100 mA
1 = 100…500 mA
2 = 200 mA…1.0 A
3 = 1.0…5.0 A
Minimum Value 0
Maximum Value 3
Default Value 3
GF WARN DELAY
(E3 Plus, Series C and later)
This parameter allows the installer to
program a time duration for which a ground
fault condition must exist at the
programmed level prior to the device
providing a warning.
Parameter Number 105
Access Rule Get/Set
Data Type USINT
Object Mapping 2Chex-1-180
Group Advanced Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 0
GF FILTER ENABLE
(FRN 5.0 and higher)
This parameter allows the installer to filter
ground fault currents from current based
protection features including Thermal
Overload, Jam, Stall, Under Load, and
Current Imbalance.
Parameter Number 131
Access Rule Get/Set
Data Type BOOL
Object Mapping 0Fhex-83-01
Group Advanced Setup
Units —
Minimum Value 0 = Disable
Maximum Value 1 = Enable
Default Value 0
➊
For use with resistive loads only. For motor loads, consult factory.
STARTS/HOUR
This parameter allows the installer to limit
the number of starts per hour.
Parameter Number 99
Access Rule Get/Set
Data Type USINT
Object Mapping 29hex-1-104
Group Advanced Setup
Units —
Minimum Value 0
Maximum Value 120
Default Value 2
STARTS INTERVAL
This parameter allows the installer to limit
the time between starts.
Parameter Number 100
Access Rule Get/Set
Data Type UINT
Object Mapping 29hex-1-105
Group Advanced Setup
Units Seconds
Minimum Value 0
Maximum Value 3600
Default Value 600