Chapter 5 Programmable Parameters
Advanced Setup Group
Table 43 - The parameters contained in the Advanced Setup Group are also
contained within the Overload Setup Group. Refer to Overload Setup Group on
page 111 for more detail on these parameters.
Table 44 - Trip Enable Parameter Detail
Table 45 - Trip Enable Bit Function Detail
Table 46 - Warning Enable Parameter Detail
TRIP ENABLE
This parameter allows the installer to
enable or disable trip functions separately.
Overload, Phase Loss, and Comm Fault are
enabled from the factory.
1 = Enabled
0 = Disabled
Parameter Number 24
Access Rule Get/Set
Data Type WORD
Object Mapping 0x29-1-124
Group Advanced Setup
Units —
Minimum Value 0000000000000000
Maximum Value 1111111111111111
Default Value 0000001000000110
Bit
Function1514131211109876543210
—
XOverload
X Phase Loss
X Ground Fault (E3 Plus)
XStall
XJam
X Underload
X PTC (E3 Plus)
X Current Imbalance
X Comm Fault
X Comm Idle
—
—
—
X Remote Trip
X Start Inhibit — Series C & Later
WARNING ENABLE
This parameter allows the installer to
enable or disable warning functions
separately. All warning functions are
disabled from the factory.
1 = Enabled
0 = Disabled
Parameter Number 25
Access Rule Get/Set
Data Type WORD
Object Mapping 0x29-1-125
Group Advanced Setup
Units —
Minimum Value 0000000000000000
Maximum Value 1111111111111111
Default Value 0000000000000000