Chapter 6 System Commissioning
Commissioning SMC-50 Soft Starter Modules
These commissioning procedures apply specifically to the SMC-50 soft starter modules.
For more information on drive commissioning for SMC-50 soft starters, refer to the appropriate user manual
listed in Additional Resources on page 15.
Apply Power to the Relay
Apply power to the SMC-50 soft starter module.
Status Indicators
The SMC-50 soft starter has one status indicator on the front of the module that displays fault and alarm codes
as described in the following table.
SMC-50 Module Status Indicator
Startup Routines
Start-up routines are available for the SMC 50 soft starter through the Start-Up Configuration Tool on the
20-HIM-A6, 20-HIM-C6S module, or the Start-Up Wizard available in DriveExplorer software. The start-up
wizard steps through general configuration.
For more information on the SMC-50 soft-starter startup routine, refer to the SMC-50 Solid-state Smart Motor
Controller User Manual, publication 150-UM011
.
Color Device Mode SMC-50 Module Status
Green Running Running without an alarm
Green/amber Running Running with an alarm
Green/flashing Ready Ready (no inhibit and no fault) without an alarm
Amber/flashing Ready Ready (no inhibit and no fault) with tuning enabled on the next start
Amber Ready Ready with alarm (no tuning enabled)
Red/amber Inhibit Inhibited, cannot start due to a Stop command
Red Faulted A non-resettable fault has occurred
Red/flashing Faulted A resettable fault has occurred
Red/green Download Firmware is being downloaded
Status Indicator