Quick Start Manual
156 Rockwell Automation Publication IASIMP-QS019E-EN-P - August 2013
Chapter 6 System Commissioning
For the Kinetix 5500 drives, apply power as required for your system configuration and observe the two status
indicators.
Module Status Indicator
Network Status Indicator
For the Kinetix 350 drives, apply 120, 240, or 460V AC mains input power to the IPD connector. If logic power
is from (24V DC) back-up power, apply backup power to the BP connector first and then apply input power.
Drive Status Indicators
Condition Status
Steady Off No power applied to the drive.
Steady Green Drive is operational. No faults or failures.
Flashing Green Standby (drive not configured).
Flashing Red
Major recoverable fault. The drive detected a recoverable fault, for example, an
incorrect or inconsistent configuration.
Steady Red Major fault. The drive detected a non-recoverable fault.
Flashing Green/Red Self-test. The drive performs self-test during powerup.
Condition Status
Steady Off No power applied to the drive or IP address is not configured.
Flashing Green Drive connection is not established, but has obtained an IP address.
Steady Green Drive connection is established. Normal operation.
Flashing Red
Connection timeout. One or more of the connections, for which this drive is the target,
has timed out.
Steady Red Duplicate IP address. IP address specified is already in use.
Flashing Green/Red Self-test. The drive performs self-test during powerup.
Status Indicator Status Status
Network
Flashing red/green or flashing green Self-test/no connections
Steady green Communication is ready
Steady or flashing red Communication error
Module
Flashing red/green or flashing green Self-test/standby
Steady green Operational condition
Steady or flashing red Drive is faulted
Axis
Flashing red/green, flashing green, flashing amber Self-test/initialization
Steady green Operational condition
Steady or flashing red Drive is faulted
Module Status
Network Status
Kinetix 5500 Servo Drive
Kinetix 350
Status Indicators