User Manual Instruction Manual

86 Rockwell Automation Publication 193-UM014B-EN-P December 2011
Appendix A
Table 25 - Electromagnetic Compatibility
Table 26 - Ethernet IP Communcations
Electromagnetic Compatibility
Electrostatic Discharge Immunity
Test Level
Performance Criteria
8 kV Air Discharge
4 kV Contact Discharge
B➊➋
RF Immunity
Test Level
Performance Criteria
10V/m: 80 MHz…1 GHz
3V/m: 1.4 GHz…2 GHz
1V/m: 2.0 GHz…2.7 GHz
B➊➋
Electrical Fast Transient/Burst Immunity
Test Level
Performance Criteria
2 kV (Power Protective Earth)
1 kV (control bus cable)
B➊➋
Surge Immunity
Test Level
Performance Criteria
1 kV L-L (bus cable)
B➊➋
Radiated Emissions Class A
Conducted Emissions Class A
Performance Criteria B requires the DUT (device under test) not to experience degradation or loss of performance.
Environment 2 - Heavy Industrial.
WARNING: This is a class A product. In domestic environment, this
product may cause radio interference, in which case the user may be
required to take adequate measures.
EtherNet/IP Communications
Total Connections Supported
TCP
CIP
150
47
Total CIP Unconnected Messages Supported 128
CIP Class 1 Connection Consumed 1
Packet Rates (packets/second)
I/O
HIM/MSG
500
500
Media Support
Twisted Pair
Fiber
Yes
No
Speed Duplex (Half/Full) 10/100
Duplicate IP Detection Yes