User Manual Instruction Manual

Rockwell Automation Publication 193-UM014B-EN-P December 2011 77
Chapter 9
Table 21 - Parameter 13 — DNet IO RPI
Table 22 - Parameter 14 — DNet IO Inhibit
Description Access Rule Data Type Units
Value
Min. Max. Default
Defines the requested packet
interval rate in milliseconds used
on DeviceNet Polled I/O
messaging.
Get/Set WORD ms 2 1000 75
Description Access Rule Data Type Units
Value
Min. Max. Default
Defines the inhibit time in
milliseconds used on DeviceNet
Change of State (COS) I/O
messaging.
Get WORD ms 2 1000 1