Table 16 - Parameter 8 — SL Entry Size
Table 17 - Parameter 9 — Device Keys
Table 18 - Parameter 10 — Scanlist Config
Table 19 - Parameter 11 — ADR Record
Table 20 - Parameter 12 — ADR Enable
Description Access Rule Data Type Units
Value
Min. Max. Default
Defines the number of bytes
to be scanned for I/O data
from each DeviceNet Device.
Get/Set USIN T Bytes 1 50 8
Description Access Rule Data Type Units
Value
Min. Max. Default
Determines how electronic
keying will be performed.
Get/Set USIN T 0 63 7
Bit
0 Device Type 2 Product Code 4 Minor Revision
1 Vendor 3 Major Revision 5 Minor of Higher
Description Access Rule Data Type Units
Value
Min. Max. Default
Triggers the building of a new
DeviceNet scan list.
0 = Ready
1 = Build Scan List
Get/Set BOOL 0 1 0
Description Access Rule Data Type Units
Value
Min. Max. Default
Triggers the recording of
configuration parameters from
devices in the DeviceNet scan list
to be used for Automatic Device
Replacement.
0 = Ready
1 = Record Parameters
Get/Set BOOL 0 1 0
Description Access Rule Data Type Units
Value
Min. Max. Default
Enables Automatic Device
Replacement.
0 = Disable
1 = Enable
Get/Set BOOL 0 1 0