Chapter 7
Logic Explicit Messaging
CompactLogix, ControlLogix, and SoftLogix controllers can read and write
specific information to and from DeviceNet modules on the same DeviceNet
network through the EtherNet/IP Communications Auxiliary using Explicit
Messaging.
The following steps configure a ControlLogix explicit message using the MSG
instruction to read diagnostic parameters from an E3 Plus Model and EC5
Overload Relay.
1. In an interger array named MSG_Read_Request, define the number of
attributes to read and list the specific attribute numbers.
The MSG instruction will return in an integer array with the first integer
representing the following information:
number of attributes
first attribute number being returned
first attribute number data status
first attribute data
last attribute number being returned
last attribute number data status
last attribute data
Scan List I/O Size Produced I/O data from the fourth scan list entry.
Scan List I/O Size Produced I/O data from the fifth scan list entry.
Scan List I/O Size Produced I/O data from the sixth scan list entry.
2 bytes Data Link 1 Data
2 bytes Data Link 2 Data
2 bytes
: :
Data Link 3 Data
: :
2 bytes Data Link 48 Data
Byte Size Contents