Quick Reference Owner manual

31
Publication 193-QR003B-EN-P - October 2009
Table 13: High Fault Short-Circuit Ratings per UL 508 and CSA 22.2, No. 14 with
NEMA contactors
Cat. No. Contactor
Size
Max. Available
Fault Current
[A]
Max.
Voltage
[V]
Max. UL Fuse [A] Circuit Breaker/
Limiter
RJ
592-EC1
592-EC2
592-EC3
592-EC5
_T 00 100000 600 20
_C
0 100000
240
30
30
FDB 3025/
LFB3070R
480
30
30
FDB 3025/
LFB3070R
600 30 30
_C 1 100000
240
60
100
FDB 3050/
LFB3035R
480
30
50
FDB 3050/
LFB3035R
600 30 50
_C 2 100000
240
100
200
FDB 3100/
LFB3150R
480 60 100
600 60 100
_D 3 100000
240 200 350
FDB 3150/
LFB3150R
480 100 200
FDB 3125/
LFB3150R
600 100 200
FDB 3100/
LFB3150R
Table 14: IFC Short-Circuit Ratings per EN60947-4-1
Cat. No. Prospective
Short-Circuit
Current I
r
[A]
Conditional
Short-Circuit
Current I
q
[A]
Max. Voltage [V]
193-EC_B, 592EC_T 1000
100000 690
193-EC_D, 592EC_C 3000
193-EC_E, 592EC_D 5000
193-EC_F 10000
193-EC_G 18000
193-EC_H 30000
193-EC_Z 1000