Quick Reference Owner manual
30
Publication 193-QR003B-EN-P - October 2009
Table 12: High Fault Short-Circuit Ratings per UL 508 and CSA 22.2, No. 14 with
Bulletin 100-C and 100-D contactors
Cat. No. Contactor Max.
Starter
FLC [A]
Max. Available
Fault Current
[A]
Max.
Voltage
[V]
Max. Class J or CC
Fuse [A]
193-EC1
193-EC2
193-EC3
193-EC4
193-EC5
_B
100-C09 9
100000 600
20
100-C12 12 20
100-C16 16 30
100-C23 23 30
_D
100-C30 30 50
100-C37 37 50
100-C43 43 70
_E
100-C60 60 80
100-C72 72 100
100-C85 85 150
FF, ZZ 100-D95 95 200
FF, ZZ 100-D110 110 200
FF, ZZ 100-D140 140 250
GF, ZZ 100-D180 180 300
GG, ZZ
100-D210 210 400
100-D250 250 400
100-D300 300 500
HG, ZZ
100-D210 210 400
100-D250 250 400
100-D300 300 500
JG, ZZ
100-D300 300 500
100-D420 420 600