Quick Reference Owner manual
26
Publication 193-QR003B-EN-P - October 2009
Table 8: Warning Summary
Warning
Function
Warning
Enable
Factory
Default
Warning Level
Settings
Warning Delay Settings Inhibit Time
Settings
Range Default Range Default Range Default
Ground Fault Disabled 0.02…5 A 2.0 A 0.0…25 s 0.0 s 0…250 s 10 s
L1
Undercurrent
Disabled 0.2…45 A — — — 0…250 s 1.0 s
L2
Undercurrent
Disabled 0.2…45 A — — — 0…250 s 1.0 s
L3
Undercurrent
Disabled 0.2…45 A — — — 0…250 s 1.0 s
L1
Overcurrent
Disabled 0.4…270 A — — — 0…250 s 1.0 s
L2
Overcurrent
Disabled 0.4…270 A — — — 0…250 s 1.0 s
L3
Overcurrent
Disabled 0.4…270 A — — — 0…250 s 1.0 s
L1 Loss Disabled — — — — 0…250 s 1.0 s
L2 Loss Disabled — — — — 0…250 s 1.0 s
L3 Loss Disabled — — — — 0…250 s 1.0 s
Comm Fault Disabled — — — — — —
Comm Idle Disabled — — — — — —
Remote Trip Disabled — — — — — —