Quick Reference Owner manual
25
Publication 193-QR003B-EN-P - October 2009
Protective Trip/Warning Summaries & Parameter Group Listing
(Cat. No. 193-EC4)
Table 7: Trip Summary
Trip
Function
Trip Enable
Factory
Default
Trip Level Settings Trip Delay Settings Inhibit Time
Settings
Range Default Range Default Range Default
Ground Fault Disabled 0.02…5 A 2.5 A 0.0…25 s 0.5 s 0…250 s 10 s
L1
Undercurrent
Disabled 0.2…45 A — 0.1…25 s 1.0 s 0…250 s 1.0 s
L2
Undercurrent
Disabled 0.2…45 A — 0.1…25 s 1.0 s 0…250 s 1.0 s
L3
Undercurrent
Disabled 0.2…45 A — 0.1…25 s 1.0 s 0…250 s 1.0 s
L1
Overcurrent
Disabled 0.4…270 A — 0.1…25 s 1.0 s 0…250 s 1.0 s
L2
Overcurrent
Disabled 0.4…270 A — 0.1…25 s 1.0 s 0…250 s 1.0 s
L3
Overcurrent
Disabled 0.4…270 A — 0.1…25 s 1.0 s 0…250 s 1.0 s
L1 Loss Disabled — — 0.5…25 s 0.5 s 0…250 s 1.0 s
L2 Loss Disabled — — 0.5…25 s 0.5 s 0…250 s 1.0 s
L3 Loss Disabled — — 0.5…25 s 0.5 s 0…250 s 1.0 s
Comm Fault Disabled — — — — — —
Comm Idle Disabled — — — — — —
Remote Trip Disabled — — — — — —