Quick Reference Owner manual

21
Publication 193-QR003B-EN-P - October 2009
The inhibit time setting parameters are applicable to both the trip and warning functions.
Overload warning setting is entered as a percentage of the thermal capacity utilized.
Must use Ground Fault Sensors (Cat. No. 193-CBCT_).
50…100% for devices with FRN 1.003 and earlier.
Available on 193/592-EC5 only.
Table 4: Warning Summary
Warning
Function
Warning
Enable
Factory
Default
Warning Level Settings Inhibit Time Settings
Range Default Range Default
Overload Disabled 0…100% 85%
Phase Loss
Ground Fault (193/592-EC2) Disabled Internal 1…5
A
2.0 A 0…250 s 10 s
Ground Fault (193/592-EC3) Disabled External
0.02…5 A
2.0 A 0…250 s 10 s
Stall
Jam Disabled 50…600% 150% 0…250 s 10 s
Underload Disabled 10…100% 70% 0…250 s 10 s
Thermistor (PTC) Disabled
Current Imbalance Disabled 10…100% 20% 0…250 s 10 s
Comm Fault Disabled
Comm Idle Disabled
Voltage Input Module
Hardware Fault r
Enabled
Under Voltage L-L r Disabled 0...65535 400 0…250 s 10 s
Over Voltage L-L Disabled 0...65535 490 0…250 s 10 s
Voltage Unbalance Disabled 0…100 85 0…250 s 10 s
Phase Rotation Disabled 1…2 1 0…250 s 10 s
Under Frequency Disabled 0…250 58 0…250 s 10 s
Over Frequency Disabled 0…250 62 0…250 s 10 s
Under Real Power Disabled 0…32767 0…250 s 10 s
Over Real Power Disabled 0…32767 0…250 s 10 s
Under Consumed kVAR Disabled 0…32767 0…250 s 10 s
Over Consumed kVAR Disabled 0…32767 0…250 s 10 s
Under Generated kVAR Disabled -32767…0 0…250 s 10 s
Over Generated kVAR Disabled -32767…0 0…250 s 10 s
Under Power kVA Disabled 0…32767 0…250 s 10 s
Over Power kVA Disabled 0…32767 0…250 s 10 s
Under Power Factor Lagging Disabled -100…0 -95 0…250 s 10 s
Over Power Factor Lagging Disabled -100…0 -90 0…250 s 10 s
Under Power Factor Leading Disabled 0...100 95 0…250 s 10 s
Over Power Factor Leading Disabled 0...100 90 0…250 s 10 s