Quick Reference Owner manual
21
Publication 193-QR003B-EN-P - October 2009
➊ The inhibit time setting parameters are applicable to both the trip and warning functions.
➋ Overload warning setting is entered as a percentage of the thermal capacity utilized.
➌ Must use Ground Fault Sensors (Cat. No. 193-CBCT_).
➍ 50…100% for devices with FRN 1.003 and earlier.
➎ Available on 193/592-EC5 only.
Table 4: Warning Summary
Warning
Function
Warning
Enable
Factory
Default
Warning Level Settings Inhibit Time Settings ➊
Range Default Range Default
Overload Disabled 0…100%➋ 85% — —
Phase Loss — — — — —
Ground Fault (193/592-EC2) Disabled Internal 1…5
A
2.0 A 0…250 s 10 s
Ground Fault (193/592-EC3) Disabled External
0.02…5 A ➌
2.0 A 0…250 s 10 s
Stall — — — — —
Jam Disabled 50…600% 150% 0…250 s 10 s
Underload Disabled 10…100%➍ 70% 0…250 s 10 s
Thermistor (PTC) Disabled — — — —
Current Imbalance Disabled 10…100% 20% 0…250 s 10 s
Comm Fault Disabled — — — —
Comm Idle Disabled — — — —
Voltage Input Module
Hardware Fault r
Enabled — — — —
Under Voltage L-L r Disabled 0...65535 400 0…250 s 10 s
Over Voltage L-L ➎ Disabled 0...65535 490 0…250 s 10 s
Voltage Unbalance ➎ Disabled 0…100 85 0…250 s 10 s
Phase Rotation ➎ Disabled 1…2 1 0…250 s 10 s
Under Frequency ➎ Disabled 0…250 58 0…250 s 10 s
Over Frequency ➎ Disabled 0…250 62 0…250 s 10 s
Under Real Power ➎ Disabled 0…32767 0…250 s 10 s
Over Real Power ➎ Disabled 0…32767 0…250 s 10 s
Under Consumed kVAR ➎ Disabled 0…32767 0…250 s 10 s
Over Consumed kVAR ➎ Disabled 0…32767 0…250 s 10 s
Under Generated kVAR ➎ Disabled -32767…0 0…250 s 10 s
Over Generated kVAR ➎ Disabled -32767…0 0…250 s 10 s
Under Power kVA ➎ Disabled 0…32767 0…250 s 10 s
Over Power kVA ➎ Disabled 0…32767 0…250 s 10 s
Under Power Factor Lagging ➎ Disabled -100…0 -95 0…250 s 10 s
Over Power Factor Lagging ➎ Disabled -100…0 -90 0…250 s 10 s
Under Power Factor Leading ➎ Disabled 0...100 95 0…250 s 10 s
Over Power Factor Leading ➎ Disabled 0...100 90 0…250 s 10 s