Quick Reference Owner manual
20
Publication 193-QR003B-EN-P - October 2009
➊ The inhibit time setting parameters are applicable to both the trip and warning functions.
➋ FLA Setting range and default values are dependent upon the current rating of the product. See the user
manual for more information.
➌ Phase loss trip level is factory-set at a current imbalance greater than or equal to 100% and is not
user-adjustable.
➍ Must use Ground Fault Sensors (Cat. No. 193-CBCT_).
➎ Stall protection is only applicable during the motor starting sequence. If any phase of current falls below the
programmed Stall Trip Level, stall protection is disabled.
➏ 50…100% for devices with FRN 1.003 and earlier.
➐ Available on 193/592-EC5 only.
Under
Consumed
kVAR ➐
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Over Consumed
kVAR ➐
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Under
Generated
kVAR ➐
Disabled -32767…0 0.1…25.0 s 1.0 s 0…250 s 10 s
Over Generated
kVAR ➐
Disabled -32767…0 0.1…25.0 s 1.0 s 0…250 s 10 s
Under Power
kVA ➐
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Over Power kVA
➐
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Under Power
Factor Lagging
➐
Disabled -100…0 -90 0.1…25.0 s 1.0 s 0…250 s 10 s
Over Power
Factor Lagging
➐
Disabled -100…0 -95 0.1…25.0 s 1.0 s 0…250 s 10 s
Under Power
Factor Leading
➐
Disabled 0...100 90 0.1…25.0 s 1.0 s 0…250 s 10 s
Over Power
Factor Leading
➐
Disabled 0...100 95 0.1…25.0 s 1.0 s 0…250 s 10 s
Table 3: Trip Summary
Trip
Function
Trip
Enable
Factory
Default
Trip Level Settings Trip Delay Settings Inhibit Time
Settings ➊
Range Default Range Default Range Default