Quick Reference Owner manual

20
Publication 193-QR003B-EN-P - October 2009
The inhibit time setting parameters are applicable to both the trip and warning functions.
FLA Setting range and default values are dependent upon the current rating of the product. See the user
manual for more information.
Phase loss trip level is factory-set at a current imbalance greater than or equal to 100% and is not
user-adjustable.
Must use Ground Fault Sensors (Cat. No. 193-CBCT_).
Stall protection is only applicable during the motor starting sequence. If any phase of current falls below the
programmed Stall Trip Level, stall protection is disabled.
50…100% for devices with FRN 1.003 and earlier.
Available on 193/592-EC5 only.
Under
Consumed
kVAR
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Over Consumed
kVAR
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Under
Generated
kVAR
Disabled -32767…0 0.1…25.0 s 1.0 s 0…250 s 10 s
Over Generated
kVAR
Disabled -32767…0 0.1…25.0 s 1.0 s 0…250 s 10 s
Under Power
kVA
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Over Power kVA
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Under Power
Factor Lagging
Disabled -100…0 -90 0.1…25.0 s 1.0 s 0…250 s 10 s
Over Power
Factor Lagging
Disabled -100…0 -95 0.1…25.0 s 1.0 s 0…250 s 10 s
Under Power
Factor Leading
Disabled 0...100 90 0.1…25.0 s 1.0 s 0…250 s 10 s
Over Power
Factor Leading
Disabled 0...100 95 0.1…25.0 s 1.0 s 0…250 s 10 s
Table 3: Trip Summary
Trip
Function
Trip
Enable
Factory
Default
Trip Level Settings Trip Delay Settings Inhibit Time
Settings
Range Default Range Default Range Default