Quick Reference Owner manual
19
Publication 193-QR003B-EN-P - October 2009
Protective Trip/Warning Summaries & Parameter Group Listing
(Cat. Nos. 193/592-EC1/EC2/EC3/EC5)
Table 3: Trip Summary
Trip
Function
Trip
Enable
Factory
Default
Trip Level Settings Trip Delay Settings Inhibit Time
Settings ➊
Range Default Range Default Range Default
Overload Enabled ➋➋Trip Class
5…30
Trip Class
10
——
Phase Loss Enabled ➌➌0.1…25.0 s 1.0 s 0…250 s 0 s
Ground Fault
(193/592-EC2)
Disabled Internal 1…5 A 2.5 A 0.0…25.0 s 0.5 s 0…250 s 10 s
Ground Fault
(193/592-EC3)
Disabled External
0.02…5 A ➍
2.5 A 0.0…25.0 s 0.5 s 0…250 s 10 s
Stall Disabled 100…600% ➎ 600% ➎ 0…250 s
➎
10 s➎ ——
Jam Disabled 50…600% 250% 0.1…25.0 s 5.0 s 0…250 s 10 s
Underload Disabled 10…100% FLA
➏
50% 0.1…25.0 s 5.0 s 0…250 s 10 s
PTC Disabled — — — — — —
Current
Imbalance
Disabled 10…100% 35% 0.1…25.0 s 5.0 s 0…250 s 10 s
Comm Fault Enabled — — — — — —
Comm Idle Disabled — — — — — —
Remote Trip Disabled — — — — — —
Voltage Input
Module
Hardware Fault
➐
Disabled — — — — — —
Undervoltage
L-L ➐
Disabled 0...65535 100 0.1…25.0 s 1.0 s 0…250 s 10 s
Overvoltage L-L
➐
Disabled 0...65535 500 0.1…25.0 s 1.0 s 0…250 s 10 s
Voltage
Unbalance ➐
Disabled 0…100 75 0.1…25.0 s 1.0 s 0…250 s 10 s
Phase Rotation
➐
Disabled 1…2 1 — — 0…250 s 10 s
Under
Frequency ➐
Disabled 0…250 57 0.1…25.0 s 1.0 s 0…250 s 10 s
Over Frequency
➐
Disabled 0…250 63 0.1…25.0 s 1.0 s 0…250 s 10 s
Under Real
Power ➐
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Over Real
Power ➐
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s