Chapter 9 –Troubleshooting and Fault Information
9-6
Table 9.A Fault Codes
Fault Description Number of Flashes HIM Fault Text HIM Fault Code Protection Fault ➀ Reset
Test 1 Trip/Test F1 Manual
Overload 2 Overload F2 ✓ Auto/ Manual
Phase Loss 3 Phase Loss F3 ✓ Manual
Ground Fault 4 Ground Fault F4 ✓ Manual
Jam/Stall 5 Jam/Stall F5 ✓ Manual
<Min.
Allowable FLC Setting
6 Illegal FLC Set F6 Manual
Non-volatile Memory Fault 7 Non Vol Memory F7 ✓ Manual
Communications Loss 8 Comm Fault F8 Manual
➀ The ✓indicates the protection faults.
Note: When the SMP-3 Auto/Manual DIP switch is in the
AUTO position, an overload fault (F2) will automatically reset
after a defined reset time (see Chapter 4 for Reset times). All
other faults must be manually reset, but they can be reset
immediately after the fault occurs.
Note: All protection faults are non-volatile. If power is
removed from the SMP-3 overload relay after a protection fault
occurs but before the fault is cleared, the SMP-3 overload relay
will power up in a faulted state once power is re-applied.