Table 6.C SMP-3 Status Data
Bit
tat
ett
xp a at
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
S
tat
us S
ett
ing E
xp
l
a
n
at
ion
X Out A 0
1
off
on
X Out B 0
1
off
on
X Control Status 0
1
Control Disabled
Control Enabled
X Connection
Indication
X Fixed (Help detect if connected)
X Not Used X XXX
X X X Analog Feedback
Designator
000
001
010
011
100
Default (Average Current)
Average Current
Thermal Capacity Utilized
Full Load Current Setting
Current Unbalance
X X X X X X X X Fault Code 0000 0000
0000 0001
0000 0010
0000 0011
0000 0100
0000 0101
0000 0110
0000 0111
0000 1000
No Fault
Trip/Test
Overload Fault
Phase Loss Fault
Ground Fault
Jam/Stall Fault
Illegal FLC Set Fault
Non-Vol Memory Fault
Comm Loss Fault
Note: The next 16 bit word following the 16 bit Status Data