Owner manual
Chapter 3 –Installation and Wiring
3-13
Short Circuit Ratings
The SMP-3 overload relay is suitable for use on a circuit
capable of delivering not more than the RMS symmetrical
amperes, 600 volts maximum, as listed in Table 3.D .
Table 3.D SMP-3 Short Circuit Ratings
Cat. No.
Maximum Available
Amperes
Maximum
Voltage
193-C1_1, -C1_T 5,000A 600V
193-C1_2, _3, _A, _C, _4, _5,
_
D, _E,
10,000A 600V
193-C1N6 18,000A 600V
193-C1P6 30,000A 600V
193-C1R6 42,000A 600V
Select the motor branch circuit protection that complies with
The National Electrical Code and any other governing regional
or local codes.
Table 3.E Wire Size and Torque Specifications
Power Terminals Control Terminals
Cat
Current
Ra ge
Min. Wire Capacity Max. Wire Capacity Torque Min. Wire Capacity Max. Wire Capacity Torque
Cat. No.
C
u
rre
n
t
Range
(A)
Metric
(mm
2
)
AWG
Metric
(mm
2
)
AWG
Lug
Nm
(Lb-in)
Wire
Nm
(Lb-in)
Metric
(mm
2
)
AWG
Metric
(mm
2
)
AWG
Nm
(Lb-in)
193-C1_1
592-C1_T
0.7-37 2.5 #14 10 #8 –
1.8
(16)
0.5 #22 (2) 2.5 (2) #14
0.8
(7)
592-C1_A 0.7-75 2.5 #14 10 #8 –
2.3
(20)
0.5 #22 (2) 2.5 (2) #14
0.8
(7)