Owner manual

Appendix A
Specifications
A-2
ELECTRICAL – CONTROL CIRCUIT (cont.)
Motor Current
Phases Three-phase or SIngle Phase
Rated Insulation Voltage 660 VAC
Maximum Operational Current (See Cat. No. Code Explanation)
Operational Frequency 50–60 Hz
Current Wave Shape Undistorted Sinusodial
ENVIRONMENTAL
Ambient Temperature
Storage –40 °C to 85 °C (–40 °F to 185 °F)
Operation (Enclosed)
(Open Enclosure)
–20 °C to 40 °C (–4 °F to 104 °F)
–20 °C to 55 °C (–4 °F to 131 °F)
Maximum Altitude 2,000 M (6,562 ft.)
Relative Humidity 5% to 95% (non-condensing)
Cooling Method Natural Convection
Vibration 1G Operational, 2.5G Non-operational
Shock 15 Operational, 30G Non-operational
Pollution Environment Degree 2
ENVIRONMENTAL (Cont.)
Terminal Marking CENELEC EN 50012
Finger Protection
(w/ contactor terminal cover)
(w/o contactor terminal cover)
(CT mounted and NEMA overload)
IP1X (Bul. 193-C1_1, 2, 3)
IP1X (Bul. 193-C1_4, 5)
IP0 (Bul. 193-C1_4, 5)
IP0 (Bul. 592 and Bul. 193-C1_6)
Electrostatic Discharge 8kV Air Discharge
RFI Susceptibility 10V/m
Fast Transient Susceptibility
2kV (AC Lines), 1kV
(Communication Lines)
Impulse Voltage Susceptibility
1kV (Line to line)
2kV (Line to ground)
Radiated Emissions CISPR11 Group 1 Class A
Conducted Emissions CISPR11 Group 1 Class A
PROTECTION FEATURES
Overload Embedded Feature
Trip Class Selectable (Class 10, 15, 20, or 30)
FLA Setting Selectable (Up to a 5:1 range)
Phase Loss Embedded Feature
Ground Fault Selectable Feature
Jam/Stall Selectable Feature